RELAY,OMRON,MY4J, 4PDT, 24VDC COIL,5A

All pictures are for illustrative purposes only.

PID# 3137

CA$7.50 EACH
Free shipping: On orders over $120 within BC

73 In Stock

Order now, processed next business day

Variants:
12VDC
24VDC
220VDC
12VAC
24VAC
110VAC
220VAC
Quantity

Request a large quantity quote

Description

Ratings

Degree of protection Closed type (cover)
Terminal structure Plug-in terminal
CoilCoil ratings 24 VDC 36.3 mA
Coil resistance 662 Ω
Operate voltage (Set voltage) 80 % max.
Release voltage (Reset voltage) 10 % min.
Maximum voltage 110 % (23 ℃)
Power consumption Approx. 0.9 W
ContactContact rated load 220 VAC 3 A (Resistive load)
220 VAC 0.8 A (Inductive load (cosφ = 0.4))
24 VDC 3 A (Resistive load)
24 VDC 1.5 A (Inductive load (L/R = 7 ms))
Max. contact voltage 250 VAC
125 VDC
Max. contact current AC: 3 A
DC: 3 A
Maximum switching power 660 VA (Resistive load)
176 VA (Inductive load (cosφ = 0.4))
72 W (Resistive load)
36 W (Inductive load (L/R = 7 ms))
Contact form 4PDT
Contact method Single
Contact material Au clad + Ag alloy

Performance

Contact resistance 50 mΩ max. (Voltage drop method with 5 VDC 1 A)
Operating time 20 ms max. (With rated operating power applied, not including contact bounce)
Reset time 20 ms max. (With rated operating power applied, not including contact bounce)
Maximum operating frequency Mechanical: 18000 time/hour
Rated load: 1800 time/hour
Insulation resistance Between coil and contacts: 100 MΩ min. (at 500 VDC)
Between contacts of different polarity: 100 MΩ min. (at 500 VDC)
Between contacts of same polarity: 100 MΩ min. (at 500 VDC)
Dielectric strength Between coil and contacts: 2000 VAC 50/60 Hz 1 min
Between contacts of different polarity: 2000 VAC 50/60 Hz 1 min
Between contacts of same polarity: 1000 VAC 50/60 Hz 1 min
Vibration resistance (destruction) 10 to 55 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude)
Vibration resistance (Malfunction) 10 to 55 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude)
Shock resistance (destruction) 1000 m/s2
Shock resistance (Malfunction) 200 m/s2
Endurance (Mechanical) 100 million operations min. (switching frequency 18,000 operations/h)
Endurance (Electrical) 200,000 operations min. (23 ℃, Rated load, switching frequency 1,800 operations/h)
Failure rate 1 VDC 1 mA (failure level: Preference value, Switching frequency: 120 operations per minute)
Ambient temperature (Operating) -55 to 70 ℃ (with no freezing or condensation)
Ambient humidity (Operating) 5 to 85 %
Weight Approx. 35 g
Mounting method Socket
Applicable socket PYF14S/ PYF14T/ PYF-14-PU/ PYF-14-PU-L/ PYFZ-14/ PYFZ-14-E/ PY14/ PY14-Y1/ PY14QN/ PY14QN2/ PY14QN-Y1/ PY14QN2-Y1/ PY14-02